1.Compliant standards
GB/T16917.1,IEC61009-1
2. Compliant certification
CCC、CE
3. Major function
Overload protection, short circuit protection, isolation, residual current operation
4. Technical parameters
Rated current(In):6A、10A、16A、20A、25A、32A、40A、50A、63A.
Rated operation voltage Ue:230V~(1P+N/2P);400V~(3P、3P+N、4P).
Rated insulation voltage Ui: 500V.
Frequency:50/60Hz.
Thermal magnetic release:C、D.
Number of poles: 1P+N、2P、3P、3P+N、4P.
Mechanical life: 20000 cycles;
Electrical life: 4000 cycles;
Rated short-circuit breaking capacity(lcn): 4.5kA、 6kA;
Short-circuit breaking capacity(lcs): 4.5kA、 6kA;
Rated impulse withstand voltage (Uimp): 4kV.
5.Dimensions and installation sizes